Article 1 
The classification system adopted at Community level for the resistance to fire performance of construction products, construction works and parts thereof shall be as set out in the Annex.
Article 2 
This Decision is addressed to the Member States.
ANNEX
The relevant definitions, tests and performance criteria are fully described in, or referenced from, the European standards referred to in this Annex.

R Load-bearing capacity
E Integrity
I Insulation
W Radiation
M Mechanical action
C Self-closing
S Smoke leakage
P or PH Continuity of power and/or signal supply
G Soot fire resistance
K Fire protection ability
D Stability duration under constant temperature
DH Stability duration under the standard time-temperature curve
F Functionality of powered smoke and heat ventilators
B Functionality of natural smoke and heat ventilators 1. The following classifications are expressed in minutes unless otherwise specified.
 2. The European standards EN 13501-2, EN 13501-3, EN 13501-4 (classification) and EN 1992-1.2, EN 1993-1.2, EN 1994-1.2, EN 1995-1.2, EN 1996-1.2, EN 1999-1.2 (Eurocodes) referred to in this Decision shall be subject to the same safeguard procedures as described in Article 5(1) of Directive 89/106/EEC.
 1. 

Applies to walls, floors, roofs, beams, columns, balconies, stairs, walkways
Standard(s) EN 13501-2; EN 1365-1,2,3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2
Classification:
R 15 20 30 45 60 90 120 180 240 360
Notes —
 2. 

Applies to Walls
Standard(s) EN 13501-2; EN 1365-1; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2
Classification:
RE  20 30  60 90 120 180 240 360
REI 15 20 30 45 60 90 120 180 240 360
REI-M   30  60 90 120 180 240 360
REW  20 30  60 90 120 180 240 360
Notes —


Applies to floors and roofs
Standard(s) EN 13501-2; EN 1365-2; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1999-1.2
Classification:
R   30       
RE  20 30  60 90 120 180 240 360
REI 15 20 30 45 60 90 120 180 240 360
Notes —
 3. 

Applies to ceilings with no independent fire resistance
Standard(s) EN 13501-2; prEN 13381-1
Classification: expressed in the same terms as the load-bearing element being protected
Notes If also fulfilling the requirement with regard to the ‘semi-natural’ fire, the symbol ‘sn’ is added to the classification.


Applies to fire protective coatings, boards, renderings, claddings and screens
Standard(s) EN 13501-2; prEN 13381-2 to 8
Classification: expressed in the same terms as the load-bearing element being protected
Notes —
 4. 

Applies to partitions (including partitions incorporating uninsulated portions, and cavity barriers)
Standard(s) EN13501-2; EN 1364-1; EN 1992-1-2; EN 1993-1-2; EN 1994-1-2; EN 1995-1-2; EN 1996-1-2; EN 1999-1-2
Classification: - 
E  20 30  60 90 120   
EI 15 20 30 45 60 90 120 180 240 
EI-M   30  60 90 120 180 240 
EW  20 30  60 90 120   
Notes —



Applies to ceilings with independent fire resistance
Standard(s) EN 13501-2; EN 1364-2
Classification:
EI 15  30 45 60 90 120 180 240 
Notes The classification is completed by ‘(a → b)’, ‘(b → a)’, or ‘(a ↔ b)’ to indicate whether the element has been tested and fulfils the requirements from above or below only or both.


Applies to facades (curtain walls) and external walls (including glazed elements)
Standard(s) EN 13501-2; EN 1364-3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2
Classification:
E 15  30  60 90 120   
EI 15  30  60 90 120   
EW  20 30  60     
Notes The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both.Where required, mechanical stability means that there are no falling parts liable to cause personal injury during the time for the E or EI classification.


Applies to raised floors
Standard(s) EN 13501-2; EN 1366-6
Classification:
R 15  30       
RE   30       
REI   30       
Notes The classification is completed by the addition of the suffix ‘f’ to indicate full fire resistance or ‘r’ to indicate exposure to the reduced constant temperature exposure only.


Applies to penetration seals and linear gap seals
Standard(s) EN 13501-2; EN 1366-3,4
Classification:
E 15  30 45 60 90 120 180 240 
EI 15 20 30 45 60 90 120 180 240 
Notes —


Applies to fire doors and shutters (including those that incorporate glazing and hardware) and their closing devices
Standard(s) EN 13501-2; EN 1634-1
Classification:
E 15 20 30 45 60 90 120 180 240 
EI 15 20 30 45 60 90 120 180 240 
EW  20 30  60     
Notes The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .



Applies to smoke control doors
Standard(s) EN 13501-2; EN 1634-3
Classification: S200 or Sa depending upon the test conditions fulfilled
Notes The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .



Applies to closures for conveyers and trackbound transportation systems
Standard(s) EN 13501-2; EN 1366-7
Classification:
E 15  30 45 60 90 120 180 240 
EI 15 20 30 45 60 90 120 180 240 
EW  20 30  60     
Notes The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. An I classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test).



Applies to service ducts and shafts
Standard(s) EN 13501-2; EN 1366-5
Classification:
E 15 20 30 45 60 90 120 180 240 
EI 15 20 30 45 60 90 120 180 240 
Notes The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use.


Applies to chimneys
Standard(s) EN 13501-2; EN 13216
Classification: G + distance in mm (e.g. G 50)
Notes Distance not required for built-in products.


Applies to Wall and ceiling coverings
Standard(s) EN 13501-2; EN 14135
Classification:
K1 10        
K2 10  30  60    
Notes
The suffixes ‘1’ and ‘2’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification.
 5. 

Applies to ventilation ducts
Standard(s) EN 13501-3; EN 1366-1
Classification:
EI 15 20 30 45 60 90 120 180 240 
E   30  60     
Notes The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. The addition of the symbol ‘S’ indicates the satisfaction of an extra restriction on leakage.


Applies to fire dampers
Standard(s) EN 13501-3; EN 1366-2
Classification:
EI 15 20 30 45 60 90 120 180 240 
E   30  60 90 120   
Notes The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbolts ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. The addition of the symbol ‘S’ indicates the satisfaction of an extra restriction on leakage.
 6. 

Applies to electrical and fibre-optic cables and accessories;conduits and fire protective systems for cables
Standard(s) EN 13501-3
Classification:
P 15  30  60 90 120   
Notes —


Applies to small diameter power or signal cables or systems (<20 mm diameter and with conductor sizes ≤2.5 mm2)
Standard(s) EN 13501-3; EN 50200
Classification:
PH 15  30  60 90 120   
Notes —
 7. 
The standards cited in this section are under preparation and may be due to revision or upgrade.


Applies to Single compartment smoke control ducts
Standard(s) EN 13501-4; EN 1363-1, 2, 3; EN 1366-9 EN 12101-7
Classification: —
E300   30  60 90 120   
E600   30  60 90 120   
Notes
The classification is completed by the suffix ‘single’ to indicate suitability for single compartment use only.In addition, the symbols, ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use.‘S’ indicates a leakage rate of less than 5 m3/hr/m2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m3/hr/m2)‘500’, ‘1 000’, ‘1 500’ indicate the suitability for use up to these values of pressure, measured at ambient.
Applies to Multi-compartment fire resistant smoke control ducts
Standard(s) EN 13501-4; EN 1363-1, 2, 3; EN 1366-8; EN 12101-7
Classification: —
EI   30  60 90 120   
Notes
The classification is completed by the suffix ‘multi’ to indicate suitability for multi-compartment use.In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use.‘S’ indicates a leakage rate of less than 5 m3/hr/m2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m3/hr/m2)‘500’, ‘1 000’, ‘1 500’ indicate the suitability for use up to these values of pressure, measured at ambient.
Applies to Single compartment smoke control dampers
Standard(s) EN 13501-4; EN 1363-1, 3; EN 1366- 9, 10; EN 12101-8
Classification: —
E300   30  60 90 120   
E600   30  60 90 120   
Notes
The classification is completed by the suffix ‘single’ to indicate suitability for single compartment use.‘HOT 400/30’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C (to be used only with E600 classification).‘ved’, ‘vew’‘vedw’ and/or ‘hod’, ‘how’‘hodw’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.‘S’ indicates a leakage rate of less than 200 m3/hr/m2. All dampers without an ‘S’ classification must have a leakage rate of less than 360 m3/hr/m2. All damper less than 200 m3/hr/m2 take this value, all dampers between 200 m3/hr/m2 and 360 m3/hr/m2 take the 360 m3/hr/m2 value. Leakage rates are both at ambient and elevated temperatures.‘500’, ‘1 000’, ‘1 500’ indicates the suitability for use up to at these values of under pressure, measured at ambient.‘AA’ or ‘MA’ indicates automatic activation or manual intervention‘i→o’, ‘i ←o’, ‘i ↔o’, indicates the performance criteria are satisfied from inside to outside, outside to inside or both respectively.‘C300’, ‘C10000’, ‘Cmod’ indicates the suitability of the damper for use in smoke control only systems combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems respectively.
Applies to Multi-compartment fire resistant smoke control dampers
Standard(s) EN 13501-4; EN 1363-1, 2, 3; EN 1366-2, 8, 10; EN 12101-8
Classification:
EI   30  60 90 120   
E   30  60 90 120   
Notes
The classification is completed by the suffix ‘multi’ to indicate suitability for multi-compartment use.‘HOT 400/30’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C.‘ved’, ‘vew’‘vedw’ and/or ‘hod’, ‘how’‘hodw’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.‘S’ indicates a leakage rate of less than 200 m3/hr/m2. All dampers without an ‘S’ classification must have a leakage rate of less than 360 m3/hr/m2. All damper less than 200 m3/hr/m2 take this value, all dampers between 200 m3/hr/m2 and 360 m3/hr/m2 take the 360 m3/hr/m2 value. Leakage rates are both at ambient and elevated temperatures.‘500’, ‘1 000’, ‘1 500’ indicates the suitability for use up to these values of pressure, measured at ambient.‘AA’ or ‘MA’ indicates automatic activation or manual intervention‘i→o’, ‘i ←o’, ‘i ↔o’, indicates that the performance criteria are satisfied from inside to outside, outside to inside or both, respectively.‘C300’, ‘C10000’, ‘Cmod’ indicates the suitability of the damper for use in smoke control only systems, combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems, respectively.
Applies to Smoke barriers
Standard(s) EN 13501-4; EN 1363-1, 2; EN 12101-1
Classification: D
D600   30  60 90 120   A
DH   30  60 90 120   A
Notes
‘A’ can be any time over 120 minutes.
Applies to Powered smoke and heat exhaust ventilators (fans), connecting joints
Standard(s) EN13501-4; EN 1363-1; EN 12101-3; ISO 834-1
Classification: F
F200       120   
F300     60     
F400      90 120   
F600     60     
F842   30       
Notes
Applies to Natural smoke and heat exhaust ventilators
Standard(s) EN 13501-4; EN 1363-1; EN 12101-2
Classification: B
B300   30       
B600   30       
Bθ   30       
Notes
Where θ indicates the exposure condition (temperature).